8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-348
YIF board failure
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace the YIF01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YIF01 board, and then load
the CMOS.BIN saved before alarm occurred.
YCP01 board failure (1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
insert the CF card which inserted original YCP01 board into the new YCP01
board.
-13
An attempt was made to access
the position data for the undefined
control group.
Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
YIF board failure
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace the YIF01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YIF01 board, and then load
the CMOS.BIN saved before alarm occurred.
YCP01 board failure (1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
insert the CF card which inserted original YCP01 board into the new YCP01
board.
-14
Position data control is not
initialized.
Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy