8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-177
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
5
The servo I/O communications
(JL098) receiving status is
incorrect. (Command timeout)
Connection failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, check the connection and insertion of the
following cables and connectors.
·EAXA01-CN517
·YSU01-CN202
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
0010
The communications loop back
value of servo I/O communications
(JL098) is incorrect.
(Communication loop back) (First
two digits show the station number
of the connected unit)
Connection failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, check the connection and insertion of the
following cables and connectors.
·AXA01-CN517
·SU01-CN202
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy