8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-215
1587
SCALE PITCH
SETTING
ERROR(SV2)
Module
failure(SERVOPACK
)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
1588
DIVIDING RATIO
SETTING
ERROR(SV2)
Module
failure(SERVOPACK
)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
1589
ENCODER
MODEL
UNMATCH(SERVO
2)
Module
failure(encoder)
Check the parameter setting, and then if it is normal, replace the encoder.
1590
MC POWER
SUPPLY WIRING
ERR(SV2)
Connection failure
Check the connection of power supply of AC/DC.
Regenerative
resistor failure
Replace the regenerative resistor.
Module
failure(SERVOPACK
)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
1591
LINEAR MOTOR
MAX SPEED
SET(SV2)
Module
failure(SERVOPACK
)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
1592
MONITOR PLD
ERROR 1(SERVO
I/O)
Circuit board
failure(YPU unit)
(1)Reset the alarm.
(2)If the alarm occurs again, replace the YPU unit. Save the CMOS.BIN
before replace the board to be safe.
1593
MONITOR PLD
ERROR 2(SERVO
I/O)
Circuit board
failure(YPU unit)
(1)Reset the alarm.
(2)If the alarm occurs again, replace the YPU unit. Save the CMOS.BIN
before replace the board to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy