rm Me
ssa
ge List
8-137
1050
SET-UP PROCESS
ERROR(SYSCON)
1
Motion instruction setup
incomplete.
YCP01 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
remove the CF from the failure YCP01 board to insert it into the new YCP01
board.
Software operation
error occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
2
Online error
YCP01 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
remove the CF from the failure YCP01 board to insert it into the new YCP01
board.
Software operation
error occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
3
SPOT management file setup
incomplete.
YCP01 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
remove the CF from the failure YCP01 board to insert it into the new YCP01
board.
Software operation
error occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy