The system program of servo
board #8 is damaged.
Software operation
error occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
EAXA board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
0060
COMMUNICATION
ERROR(I/O
MODULE)
0
The IO module board connected
with 0th serial bus exists.
Software operation
error occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
YIF board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YIF01 board, and then load
the CMOS.BIN saved before alarm occurred.
1
An error was detected in
communications with the I/O
module board connected with 1st
serial bus when the control power
turned ON.
Setting error
(1)Check the following settings.
· The rotary switch setting which specifies slot numbers of each I/O module
· I/O module settings in maintenance mode
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following cables and connectors.
· The MII communications cable which I/O module of the corresponding node
number
· (In case of MII communications last station) Terminator
· 24V power of the corresponding I/O module
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy