Protective Elements
Parameter
Description
Setting range
Default
Menu path
t-reset
Reset time for inverse characteristics.
Only available if: Characteristic = INV
0.0 - 1000.0s
1.0s
[Protection
Para
/<1..4>
/V/f>-Prot
/V/f>[1]]
Input States of the Volts/Hertz Element
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/V/f>-Prot
/V/f>[1]]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/V/f>-Prot
/V/f>[1]]
ExBlo TripCmd-I
Module input state: External Blocking of the Trip
Command
[Protection Para
/Global Prot Para
/V/f>-Prot
/V/f>[1]]
Signals of the Volts/Hertz (Output States)
Signal
Description
active
Signal: active
ExBlo
Signal: External Blocking
Blo TripCmd
Signal: Trip Command blocked
ExBlo TripCmd
Signal: External Blocking of the Trip Command
Alarm
Signal: Alarm Overexcitation
Trip
Signal: Trip
TripCmd
Signal: Trip Command
766
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...