Protective Elements
Parameter
Description
Setting range
Default
Menu path
Blo TripCmd
Permanent blocking of the Trip Command of
the module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
ExBlo TripCmd
Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo TripCmd
Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
Id min
Constant minimum pickup current
(differential current). Pickup value of the
differential current based on the rated
current Ib of the protection object.
0.05 - 1.00Ib
0.2Ib
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
Id(Is0)
Starting point of the static tripping
characteristic at Is0
0.0 - 1.00Ib
0.0Ib
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
Id(Is1)
Breaking point of the static tripping
characteristic at Is1
0.2 - 2.00Ib
0.6Ib
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
Id(Is2)
Value of the static tripping characteristic at
Is2
1.0 - 8.0Ib
6.2Ib
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
Is1
Breaking point of the static tripping
characteristic when Is1
0.5 - 4.0Ib
2.0Ib
[Protection
Para
/<1..4>
/Diff-Prot
/Id]
636
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...