Switchgear/Breaker – Manager
Trip Manager – Assignment of commands
The trip commands of the protection elements have to be assigned to those switchgear, that are make/break
capable (Circuit Breaker). For every make/break capable switchgear a Trip Manager is provided.
In the Trip Manger all tripping commands are combined by an “OR” logic. The actual tripping command to the
switchgear is exclusively given by the Trip Manager
. This means, that only tripping commands which are assigned
in the Trip Manager lead to an operation of the switchgear.
In addition to that, the User can set the minimum hold
time of the tripping command within this module and define whether the tripping command is latched or not.
507
MCDLV4
DOK-HB-MCDLV4-2E
Aux ON-I
Aux OFF-I
Ready-I
SG[x].OFF Cmd1
SG[x].OFF Cmd2
SG[x].OFF Cmd3
S
G
[x
]
OFF Cmd
ON Cmd
TripCmd
Prot ON
I[1].TripCmd
I[2].TripCmd
I[3].TripCmd
I
P
ro
te
ct
io
n
M
od
u
le
V[1].TripCmd
V[2].TripCmd
V[3].TripCmd
V
P
ro
te
ct
io
n
M
o
d
u
le
HMI
Autoreclosure CLOSE
Command
Scada
* Availability dependent on
device type
*
*
A
va
ila
b
ili
ty
d
ep
en
de
nt
o
n
de
vi
ce
t
yp
e
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...