Protective Elements
Please be aware of the meaning of the two delay timers.
t load Off (Pickup Delay): After this time expires, the load is no longer
diversified.
t Max Block (Release Delay): After the starting condition is fulfilled (e.g.:
breaker switched on manually), the “CLPU.enabled” signal will be issued for
this time. That means for the duration of this time, the tripping thresholds of the
overcurrent protection can be desensitized by means of adaptive parameters
(please refer to the Parameters section). This timer will be stopped if the
current falls below 0.9 times of the threshold of the load inrush detector and
remains below 0.9 times of the threshold for the duration of the settle time.
This Notice applies to protective devices that offer control functionality only!
This protective element requires, that a switchgear (circuit breaker is assigned
to it. It is allowed only to assign switchgears (circuit breaker) to this protective
element, whose measuring transformers provide measuring data to the
protective device.
775
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...