Service and Commissioning Support
Device Planning Parameters of the Failure Simulator
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
use
[Device planning]
Global Protection Parameter of the Failure Simulator
Parameter
Description
Setting range
Default
Menu path
PreFault
Pre Fault Duration
0.00 - 300.00s
0.0s
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/Times]
FaultSimulation Duration of Fault Simulation
0.00 -
10800.00s
0.0s
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/Times]
PostFault
PostFault
0.00 - 300.00s
0.0s
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/Times]
TripCmd Mode
Trip Command Mode
No TripCmd,
With TripCmd
No TripCmd
[Service
/Test (Prot
inhibit)
/Sgen
/Process]
Ex Start
Simulation
External Start of Fault Simulation (Using the
test parameters)
1..n,
Assignment List
-.-
[Service
/Test (Prot
inhibit)
/Sgen
/Process]
1124
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...