Protective Elements
Example: Direct Trip Transfer
If it is required that a trip decision of the phase differential protection of the remote device always trips the local
device as well then this can be achieved with the Transfer Trip („Trip-Trans“) module.
The trip signals („Trip“) of the phase differential protection “Id” and of the unrestrained high-set differential current
protection “IdH” must be assigned to the transmission inputs of the Transfer Trip module.
Then the trip command (TripCmd) of the Transfer Trip module has to be assigned as an additional trip command
(Off Cmd) to the Trip Manager of the switchgear so that it can finally be assigned to an output relay to trigger the
tripping coil.
670
MCDLV4
DOK-HB-MCDLV4-2E
T
ra
n
sf
e
rT
ri
p
s_
Z
0
1
A
B
CT A
Device A
Device B
QA
QB
CT B
Trip-Trans
Trip 1
Trip 1
Trip 2
Trip 2
Transmit
Receive
TripCmd
Permissive 1
Permissive 2
Φ
ExBlo1
ExBlo2
QA
TripCmd
Off Cmd 1
Off Cmd 2
Off Cmd 3
BO 1
Assignment
1
Trip-Trans
Trip 1
Trip 1
Trip 2
Trip 2
Transmit
Receive
TripCmd
Permissive 1
Permissive 2
Φ
ExBlo1
ExBlo2
QB
TripCmd
Off Cmd 1
Off Cmd 2
Off Cmd 3
BO 1
Assignment
1
Id
Alarm
Trip
TripCmd
Alarm
Trip
TripCmd
ExBlo1
ExBlo2
IdH
Alarm
Trip
TripCmd
Alarm
Trip
TripCmd
ExBlo1
ExBlo2
Assignment
Assignment
Id
Alarm
Trip
TripCmd
Alarm
Trip
TripCmd
ExBlo1
ExBlo2
IdH
Alarm
Trip
TripCmd
Alarm
Trip
TripCmd
ExBlo1
ExBlo2
TripCmd
TripCmd
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...