![background image](http://html1.mh-extra.com/html/woodward/highprotec-mcdlv4/highprotec-mcdlv4_manual_995884501.webp)
Switchgear/Breaker – Manager
Withdrawable Circuit Breaker (Draw Out Circuit Breaker)
The truck of a withdrawable circuit breaker has to be managed as an individual switchgear. There is no fixed
connection between the circuit breaker and the truck. An interlocking has to be set by the User because it is not
allowed to withdraw the breaker as long as it is in the closed position. The circuit breaker can be switched in the
withdrawn and in the non-withdrawn position.
The signals of the control circuit (low voltage) plug have to be wired and configurated with(-in) the protective device.
The control (supervision) will be set to »Removed«
W
hen the control circuit plug is removed (pulled).
The circuit breaker will be set into the »CB OFF«-position as long as the »Removed«-signal is active.
It´s not possible to manipulate the Position Signals of a withdrawn (removed) circuit
breaker.