Supervision
Commissioning: Loss of Potential (FF via DI)
Object to be tested:
Check if the auto fuse failure is correctly identified by the device.
Procedure
•
Turn off the automatic circuit breaker of the VTs (all poles to be dead)
Successful test result
•
The state of the respective digital input changes.
•
All protective elements are blocked which should not have an unwanted operation caused by a fuse failure
»
Measuring Circuit Supervision=active«.