Protective Elements
Voltage Controlled Overcurrent Protection [51C]
When a sort circuit is near the generator, the voltage might drop down. By means of
Adaptive Parameters (Please
refer to chapter Parameter) the tripping times or tripping characteristics can be modified by the output signal of a
voltage element (depending on a threshold). The device might change a load curve to a fault curve (taking
influence on tripping time, trip curves and reset modes).
Please proceed as follows:
Read and understand the section „Adaptive Parameters“ within the chapter Parameter.
Do the device planning and set all required parameters for the Undervoltage element.
Do the device planning and set all required parameters for the Overcurrent element.
Set the
Adaptive Parameters within the Overcurrent element in the relevant parameter sets (e.g. Curve
multiplier, curve type...).
Assign the Undervoltage alarm (pickup) within the
Global Parameters as an activation signal for the
corresponding
Adaptive Parameter set of the overcurrent element that should be modified.
Check the functionality by a commissioning test.
710
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...