Protective Elements
Functional Principle of the LVRT
From the grid operators point of view, a
LVRT profile defines a voltage profile which a distributed energy resource,
that is connected to the grid, should be able to ride through in case of a low voltage event (voltage dip). The
distributed energy resource is only allowed to disconnect from the grid if the voltage at the point of common
coupling drops below the
LVRT borderline. In other words, a LVRT protection function is a time-dependent voltage
supervision according to a predefined voltage profile. The time-dependent voltage supervision will be started, as
soon as the voltage at the point of common coupling falls below the start voltage level. The
LVRT will be stopped,
as soon as the voltage rises above the recover voltage level.
962
MCDLV4
DOK-HB-MCDLV4-2E
V
ol
ta
ge
[
%
]
Short Circuit Duration [s]
Source: eBWK Bd. 60 (2008) Nr. 4
Authors: Dipl.-Ing. Thomas Smolka, Dr.-Ing. Karl-Heinz Weck, Zertifizierungstelle der FGH e.V., Mannheim, sowie Dipl.-Ing. (FH) Matthias Bartsch,
Enercon GmbH, Aurich.
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...