Protective Elements
The following table shows the application options of the voltage protection element
Applications of the V-Protection Module
Setting in
Option
ANSI 27 Undervoltage protection
Device Planning menu
Setting: V<
Measuring Method:
Fundamental/TrueRMS
Measuring Mode:
Phase to ground, Phase-to-Phase
10 minutes sliding average supervision V<
Device Planning menu
Setting: V<
Measuring Method: Umit
Measuring Mode:
Phase to ground, Phase-to-Phase
ANSI 59 Overvoltage protection
Device Planning menu
Setting: V>
Measuring Method:
Fundamental/TrueRMS
Measuring Mode:
Phase to ground, Phase-to-Phase
Sliding average supervision V>
Device Planning menu
Setting: V>
Measuring Method: Vavg
Measuring Mode:
Phase to ground, Phase-to-Phase
Measuring Method
For all protection elements it can be determined, whether the measurement is done on basis of the »
Fundamental«
or if »
TrueRMS« measurement is used. In addition to that a sliding average supervision »Vavg« can be
parametrized.
The required settings for the calculation of the “average value” of the “sliding
average value supervision” have to be taken within menu
[Device Para\Statistics\Vavg].
Measuring Mode
If the measuring inputs of the voltage measuring card is fed with “Phase to Ground” voltages, the Field Parameter
»VT con« has to be set to “Phase to Ground”. In this case, the user has the option to set the »Measuring Mode« of
each phase voltage protection element to“Phase to Ground” or “Phase to Phase”. That means, he can determine for
each phase voltage protection element how Vn shall be defined:
•
»Measuring Mode« = “Phase to Ground” –
Vn
=
VT sec
√
3
•
»Measuring Mode« = “Phase to Phase” –
Vn
=
VT sec
If, however, the measuring inputs of the voltage measuring card are fed with “Phase to Phase” voltages (
»VT con«
= “Phase to Phase”), then the setting of
»Measuring Mode« is ignored and internally set to “Phase to Phase”
instead, so that
Vn
=
VT sec
.
825
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...