Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Disarm Mode
CAUTION! RELAYS DISARMED in order to
safely perform maintenance while
eliminating the risk of taking an entire
process off-line. (Note: The Supervision
Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN
after maintenance.
permanent,
timeout
permanent
[Service
/Test (Prot
inhibit)
/DISARMED
/BO Slot X2]
t-Timeout
DISARM
The relays will be armed again after
expiring of this time.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test (Prot
inhibit)
/DISARMED
/BO Slot X2]
Force Mode
By means of this function the normal Output
Relay States can be overwritten (forced) in
case that the Relay is not in a disarmed
state. The relays can be set from normal
operation (relay works according to the
assigned signals) to "force energized" or
"force de-energized" state.
permanent,
timeout
permanent
[Service
/Test (Prot
inhibit)
/Force OR
/BO Slot X2]
t-Timeout Force The Output State will be set by force for the
duration of this time. That means for the
duration of this time the Output Relay does
not show the state of the signals that are
assigned on it.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test (Prot
inhibit)
/Force OR
/BO Slot X2]
126
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...