Instructions for Digitrip  RMS 510 Trip Unit 

Table of Contents 

Page 

1. 0 
1.1 
1. 2 
1. 3 
2.0 

3.0 
3. 1 
3. 2 
3. 3 

3.4 
3.5 
3. 6 

4. 0 
4.1 
4.2 
4. 3 
4.4 

4.5 
4.6 

4.7 
4. 8 
4.9 

5. 0 
5. 1 
5.2 
5. 3 

5.4 
5.4.1 
5.4. 2 
5.4.3 

6. 0 
6. 1 
6. 2 
6.3 
7. 0 

8. 0 

9. 0 
9. 1 
9. 2 

9.3 
9.4 

General Description  .. . . . . . ... . ... .

.

. . .. .  1 

Protection  . ..... . . .. .. . .

.

. . ... . . . . . . . . .  1 

Information  . ... . . .. . .

.

.. .

.

. .

.

.

.

. .. . . .. .  2 

Testing . . . . . . . .. . . . . .

.

. . .

.

. . .. . .... . .

.

.  4 

UL Listed Devices . . . . . .. . ..

.

. .. . . .. . .... 4 

Principle of Operation .. ... . . . ..

.

. .

.

.

... . .  4 

General ..

.

. ... . . . . ... . . . ....

.

. .. . . .. .. 4 

Trip and Operation  Indicators . . . . .. .. . . ..

.

.  5 

Test Provisions  .

.

. ..

.

. .

.

.

.

. . . . .. .. .

.

... . 5 

DIScriminator (Making Current Release)  . ... . 5 
OV ERRIDE (Fixed  Instantaneous) . . . .... ...  6 

Zone Interlocking . . .

.

.

. . . .. . .

.

. . .. .... . . .  6 

Protection Settings . . .

.

. . .... ... . .. . ..

.

. .  6 

General . .

.

.. . ... . .

.

.

. .

.

.. . ... . .. . ... . .  6 

Long Delay Current Settings .. . . .. ... . ... . .  7 
Long Delay Time Settings . ... .. .. ... . .... . 7 

Short Delay Current Settings  . . . ... ... . ....  8 
Short Delay Time Settings  .. . . . . .....

.

. ... 8 

Instantaneous Current Settings . . . . . . .. . . .. .  8 

NO  Instantaneous Current Settings  .

.

. ..

.

.

.

. 8 

Ground Fault Current Settings 

.

. .

.

. . .. . .

.

..  8 

Ground Fault Time Delay Settings 

.

..

.

.

. . . .

Test Procedure  . .

.

.

.

.

.

.

. . .... . ... . .. . . .  10 

General ... . .. .. . . .

.

.

. ..

.

. . . ... . ..

.

. ..  10 

When To Test  ...

..

.. . . ... . . .... ...

.

.

..  11 

Test Provision . .

.

.

.

. . . . .. . .. .

.

.

.

...

.

. .

11 

Conducting Tests .

.

. . .. . .. . .... .

.

. ...

.

.

11 

Control Power . . . . .. . . . . .. .. .

.

. .

.

.. .

.

.

11 

Not Tripping the Breaker . . .. ..

.

....

.

.

. .

.

12 

Tripping the Breaker . ..

.

.. .

.

.

.

.

.

.

. .

.

. . . .  12 

Battery (Inside the Rating Plug)  .

.

.

.

.

. . .. . .  12 

General .

.

. ... .. . .. .

.

. . .. .

.

. .

.

. ... .

.

..  12 

Battery Check . . . ..

.

. . ... . .. . .

.

. . .. .. ..  12 

Battery Replacement  .. . . . ...

.

. .. . .. . . ..  12 

Auxiliary Power Module . . . . . . ...... . ... . .  14 

Frame Ratings,  (where applicable, 

Sensor Ratings) and Rating  Plugs . . . ... . .  14 

References . . . . . . ..

.

. . . .. .. . . . .. . .

.

.. .  15 

Digitrip RMS Trip Assemblies 

.

.. . .. . .. . . .. 15 

Type OS Low Voltage AC Power Circuit 

Breakers . ... . . . . ... . .

.

. . . .

.

. ... . ... .  15 

Type SPB Systems Pow-R Breakers . .. . .... 15 
Series C1.4 

® 

R-Frame  Molded Case Circuit 

Breakers  .... .. . . . . ..

.

. ..... . . . . . ... 15 

Appendix A Zone Interlocking - Example . .. . . ... . ..  15 

Effective May 1997,  Supersedes 

I.L. 

29·885A dated September 1994 

WARNING 

DO NOT ATTEM PT TO INSTALL OR PERFORM MAIN­
TENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. 

DEATH OR  SEVERE PERSONAL INJURY CAN 
RESULT FROM  CONTACT  WITH ENERGIZED EQUIP­
MENT. ALWAYS VERIFY THAT NO VOLTAGE IS 

PRESENT BEFOR E  PROCEEDING  WITH THE TASK, 
AND ALWAYS FOLLOW GENERALLY  ACCEPTED 
SAFETY PROCEDURES. CUTLER-HAMMER I S  NOT 
LIABLE FOR THE MISAPPLICATION  OR MISINSTAL­
LATION OF ITS PRODUCTS. 

It is strongly urged that the user observe all recommen­

dations, warnings and cautions relating to the safety of 
personnel and equipment, as well as general and local 

health and safety laws, codes, and procedures. 

The recommendations and information contained herein 

are based on experience and judgment, but should not 
be considered to be all-inclusive or covering every appli­
cation or circumstance which may arise.  If you have any 
questions or need further information or instructions, 
please contact your local representative, or the Customer 

Support Center for the type of circuit breaker you have: 

Circuit 

Call 

Send to 

Breaker 

Telephone 

FAX 

Type 

Number 

Number 

DS/OSL 

(412)  937-6029 

(412)  937-6396 

SPB 

(412)  937-6029 

(412)  937-6396 

Series 

c® 

R-Frame 

(412)  937-6490 

(412)  937-6010 

1.0 

GENERAL DESCRIPTION 

1.1 

Protection 

The Digitrip RMS 51 0, illustrated in Fig. 

1, 

is a custom 

application specific integrated circuit based trip unit suit­

able for use in types OS and DSL low voltag,e AC power 
circuit breakers and type SPB Systems Pow-R circuit 

breakers and Series 

c® 

R-Frame molded case circuit 

breakers. 

The Digitrip RMS 510 provides true RMS current sensing 

for proper correlation with thermal characteristics of con­

ductors and equipment.  Interchangeable rating plugs are 

provided to establish the continuous current rating of 
each circuit breaker. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Cutler-Hammer Digitrip RMS 510 Trip Unit

Page 1: ...ILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES CUTLER HAMMER IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTAL LATION OF ITS PRODUCTS It is strongly urged that the user observe all recommen dations warnings and cautio...

Page 2: ...protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PROTECTION Refer to the National Electric Code for appropriate application of 4 pole breakers 1 2 Information Light Emitting Diodes LED s on the face of the trip unit light Red to indicate the reason for an automatic trip operation The battery in the rating plug maintains the reason for trip indication followi...

Page 3: ...Protection LI Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection LIG w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 4: ...me Instantaneous Ground Protection LSIG The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 Individual product instruction leaflets referenced in Section 9 0 illus trate typical Digitrip RMS Trip Units installed in specific breakers T he trip unit employs the Cutler Hammer Inc custom designed...

Page 5: ...0 of the frame current sensor rating the green LED will flash On and Off onceeach second to indicate the trip unit is energized and operating properly Note If the LED is steadily GREEN i e not flash ing the trip unit is not ready Effective May 1997 3 3 Test Provisions See Section 5 0 3 4 DIScriminator Making Current Release For Types LS and LSG trip units only When the Digitrip RMS 510 Trip Unit i...

Page 6: ...ream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 8858 Note If a breaker M receives a Zone Interlocking signal from another breaker F but the fault current level is less than the trip unit setting for breaker M the signal from the other breaker F will no...

Page 7: ... earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 10 minutes it has reset fully so that next Long Delay trip time will again be the Set ting value In certain applications it may be desirable to dis able the LTM function The LTM function can be disabled by first opening the breaker and then removing the Rating Plug See Figures ...

Page 8: ...licable to currents less than eight 8 times 1 the Long Delay Setting For currents greater than 8 times 1 the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Setting There are eight 8 available Instantaneous Current Set tings as illustrated in Fig 4 5 Six settings are in the range from 2 to 6 times In the rating plug value and th...

Page 9: ...0 240 300 400 a w 600 150 180 210 240 300 360 450 600 Q_ 630 158 189 221 252 315 378 473 630 s 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 J 400 500 600 750 1000 _J 1200 300 360 420 480 600 720 900 1200 Q_ 9 1250 312 375 438 500 625 750 936 1200 z 1600 400 480 560 640 800 960 1200 1200 a 2000 500 600 700 800 1000 1200 1200 1200 0 2400 600 720 840 960 1200 1200 1200 1200 w _J _J 2500 625...

Page 10: ...utomatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip Unit A CAUTION TESTING A CIRCUIT BREAKER UNDER TRIP CON DITIONS WHILE IT IS IN SERVICE AND CARRYING LOAD CURRENT WHETHER DONE BY INTERNAL OR EXTERNAL MEANS IS NOT RECOMMENDED ANY TRIPPING OPERATION WILL CAUSE DISRUP TION OF SE...

Page 11: ...s than10 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indicating that there is enough current flowing to pro vide the power necessary to operate the trip unit In the event the Unit Status LED is either lighted GREEN or OFF continuously there is NOT enough cur rent flowing to power ...

Page 12: ...ng make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting lr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current exceeds 50 of lr 2 Place the Test Amps selector switch See Fig 5 in one of the two Trip test settings i e 6T or GFT 3 Depress the black Test pushbutton See Fig 5 and release it the test is initiated when ...

Page 13: ...r Rat1ng Plug Identification Fig 6 Battery Check Pushbutton 1 Typical Rating Plug Values for Sho t Delay S1 and S2 Instantaneous M1 and M2 Set11llQS Battery OK if LED lights GREEN when Battery Check Button is Pushed Page 13 obtained from the following companies under their type designation indicated Company Model Varta Batteries Inc 150 Clarbrook Road Elmsford N Y 10523 Duracell South Broadway Tar...

Page 14: ...cuit breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity to complete the trip unit See Fig 1 Rating plugs have two current ratings listed on their covers See Fig 6 1 the Must be used with Frame Rated cur I L 29 8858 rent value or Sensor Rated if applica b...

Page 15: ...me Circuit Breaker APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used The branch breaker will trip clearing the fault in 0 1 s Fault 2 The feeder breaker will trip clearing the fault in 0 3 s Fault 1 The breaker will trip clearing the fault in 0 5 s CASE 2 There is Zo...

Page 16: ...he maximum distance between first and last zone is 250 feet 110 m A3 A Maximum of 20 breakers may be con nected in parallel in one Zone Legend Common Ungrounded Short Delay Output Signal to Higher Level Zone Short Delay Input Signal from Lower Level Zone Ground Output Signal to Higher Level Zone Ground Input Signal from Lower Level Zone ault at Location 2 2 M2 0 5 Sec F21 F22 F23 0 1 Sec 0 1 Sec 0...

Page 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 19: ...I L 29 8858 Page 19 0 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 20: ...OSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer Inc be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any special indirect incidental or consequential damage or loss whatsoever incl...