Technical Data
Technical Data
Use Copper conductors only, 75°C.
Conductor size AWG 14 [2.5 mm
2
].
Climatic Environmental Conditions
Storage Temperature:
Operating Temperature:
-30°C up to +70°C (-22°F to 158°F)
-20°C up to +60°C (-4°F to 140°F)
Permissible Humidity at Ann. Average:
<
75% rel. (on 56d up to 95% rel.)
Permissible Installation Altitude:
<2000 m (6561.67 ft) above sea level
If 4000 m (13123.35 ft) altitude apply a changed classification of
the operating and test voltages may be necessary.
Degree of Protection
EN 60529
HMI front panel with seal
IP54
HMI front panel without seal
IP50
Rear side terminals
IP20
Routine Test
Insulation test acc. to IEC60255-5:
All tests to be carried out against earth and other input- and
output circuits
Aux. voltage supply, digital inputs,
current measuring inputs, signal relay
outputs:
2.5 kV (eff) / 50 Hz
Voltage measuring inputs:
3.0 kV (eff) / 50 Hz
All wire-bound communication interfaces: 1.5 kV DC
1137
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...