Communication Protocols
Time Synchronization
Time and date of the relay can be set by means of the time synchronization function of the IEC60870-5-103
protocol. If the time synchronization signal is send out with a confirmation request, the device will answer with a
confirmation signal.
Spontaneous Events
The events that are generated by the device will be forwarded to the master with numbers for standard function
types / standard information. The data point list comprises all events that can be generated by the device.
Cyclic Measurement
The device generates on a cyclic base measured values by means of ASDU 9. They can be read out via a class 2
query. Please take into account that the measured values will be send out as multiples (1.2 or 2.4 times the rated
value). How to set 1.2 or 2.4 as multiplier for a value can be taken from the data point list.
The parameter “Transm priv meas val” defines if additional measurement values should be transmitted in the private
part. Public and private measured values are transmitted by ASDU9. That means that either a “private” or a “public”
ASDU9 will be transmitted. If this parameter is set, the ASDU9 will contain additional measured values that are an
enhancement of the standard. The “private” ASDU9 is send with a fixed function type and information number that
does not depend the type of device. Please refer to the data point list.
Commands
The data point list comprises a list of the supported commands. Any command will be responded by the device with
a positive or negative confirmation. If the command is executable, the execution with the corresponding reason for
the transmission (COT) will be lead in at first, and subsequently the execution will be confirmed with COT1 within a
ASDU9.
Disturbance Recording
The disturbances recorded by the device can be read out by means described in standard IEC60870-5-103. The
device is in compliance with the VDEW-Control System by transmission of an ASDU 23 without disturbance records
at the beginning of an GI-Cycle.
A disturbance record contains the following information:
Analog Measured Values, IL1, IL2, IL3, IN, Voltages VL1, VL2, VL3, VEN;
Binary States, transmitted as marks, e.g. Alarms and Trips.
The Transmission ratio will not be supported. The transmission ratio is included in the “Multiplier”.
Blocking the Transmission in Monitor Direction
The relay supports the function to block the transmission in monitor direction. There are two ways to activate this
blocking:
•
Manual activation via Direct Control parameter
»Activate Block MD«
•
External activation, by assigning a signal to the setting parameter
»Ex activate Block MD«
Test Mode
The relay supports the test mode (Cause of Transmission 7). There are two ways to activate the test mode:
•
Manual activation via Direct Control parameter
»Activate test mode«
•
External activation, by assigning a signal to the setting parameter
»Ex activate test mode«
322
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...