Protective Elements
Parameter
Description
Setting range
Default
Menu path
Shots
Maximum number of permitted reclosure
attempts.
1 - 6
1
[Protection
Para
/<1..4>
/AR
/General
Settings]
Initiate Mode
Initiate Mode
Alarm,
TripCmd
Alarm
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-start
Start timer - While the start timer runs
down, an AR attempt can be started. Only if
the trip command is given within the start
time/duration an AR attempt could be
started. The location and the resistance of
the fault have a big influence on the tripping
time. The start time has an impact on
whether an AR attempt should be started
when the fault is far away or high
resistance.
Only available if: Initiate Mode = TripCmd
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-DP1
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 1-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl1]
t-DP2
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 2-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl2]
t-DP3
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 3-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl3]
802
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...