Protective Elements
Trip Direction of the Under Frequency Load Shedding
Definitions
Load Flow Arrow System = Consumed active and reactive are counted positive (greater than zero)
Generator Flow Arrow System = produced power is to be counted positive (greater than zero)
By means of the parameter »
P Block dir« a sign reversal can be applied to the active power within the UFLS
module. Protective devices that use the load flow arrow (like the MCA4 or the MRA4) are to be set to »
Power Trip
dir= negative«. Protective devices that are working on the base of the generator flow arrow system to be set to
»
Power Trip dir= positive«.
949
MCDLV4
DOK-HB-MCDLV4-2E