Time Synchronization
Selection of Timezone and Synchronization Protocol
The protection relay masters both UTC and local time. This means that the device can be synchronized with UTC
time while using local time for user display.
Time Synchronization with UTC time (recommended):
Time synchronization is usually done using UTC time. This means for example that an IRIG-B time generator is
sending UTC time information to the protection relay. This is the recommended use case, since here a continuous
time synchronization can be ensured. There are no “leaps in time” through change of summer- and wintertime.
To achieve that the device shows the current local time, the timezone and the change between summer- and
wintertime can be configured.
Please carry out the following setting steps under [Device Para/ Time]:
1.Select your local timezone in the timezone menu.
2.There also configure the switching of daylight saving time.
3.Select the used time synchronization protocol in the TimeSync menu (e.g. “IRIG-B”).
4.Set the parameters of the synchronization protocol (refer to the according chapter).
Time Synchronization with local time:
Should the time synchronization however be done using local time, then please leave the timezone to »
UTC+0
London« and do not use switching of daylight saving time.
The synchronization of the relay's system time is exclusively done by the
synchronization protocol selected in the menu [Device Para/ Time/ TimeSync/
Used Protocol].
Without Time Synchronization:
To achieve that the device shows the current local time, the timezone and the change between summer- and
wintertime can be configured.
Please carry out the following setting steps under [Device Para/ Time]:
1. Select your local timezone in the timezone menu.
2. There also configure the switching of daylight saving time.
3. Select »
manual« as your used protocol in the TimeSync menu.
4. Set date and time.
396
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...