Service and Commissioning Support
Parameter
Description
Setting range
Default
Menu path
phi VL2
Start Position respectively Start Angle of the
Voltage Phasor during Fault-Phase:phase L2
-360 - 360°
240°
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/
FaultSimulation
/VT]
phi VL3
Start Position respectively Start Angle of the
Voltage Phasor during Fault-Phase:phase L3
-360 - 360°
120°
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/
FaultSimulation
/VT]
phi VX meas
Start Position respectively Start Angle of the
Voltage Phasor during Fault-Phase: VX
-360 - 360°
0°
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/
FaultSimulation
/VT]
VL1
Voltage Fundamental Magnitude during Post
phase: phase L1
0.00 - 2.00Vn
0.57Vn
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/PostFault
/VT]
VL2
Voltage Fundamental Magnitude during Post
phase: phase L2
0.00 - 2.00Vn
0.57Vn
[Service
/Test (Prot
inhibit)
/Sgen
/Configuration
/PostFault
/VT]
1128
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...