Protective Elements
Module Automatic Reclosure Signals (Output States)
Signal
Description
active
Signal: active
ExBlo
Signal: External Blocking
Standby
Signal: Standby
t-Blo after CB man ON
Signal: AR blocked after circuit breaker was switched on manually. This
timer will be started if the circuit breaker was switched on manually. While
this timer is running, AR cannot be started.
Ready
Signal: Ready to shoot
running
Signal: Auto Reclosing running
t-dead
Signal: Dead time between trip and reclosure attempt
CB ON Cmd
Signal: CB switch ON Command
t-Run2Ready
Signal: Examination Time: If the Circuit Breaker remains after a reclosure
attempt for the duration of this timer in the Closed position, the AR has
been successful and the AR module returns into the ready state.
Lock
Signal: Auto Reclosure is locked out
t-Reset Lockout
Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout
state will be delayed for this time, after the reset signal (e.g digital input or
Scada) has been detected .
Blo
Signal: Auto Reclosure is blocked
t-Blo Reset
Signal: Delay Timer for resetting the AR blocking. The release (de-blocking)
of the AR will be delayed for this time, if there is no blocking signal
anymore.
successful
Signal: Auto Reclosing successful
failed
Signal: Auto Reclosing failure
t-AR Supervision
Signal: AR Supervision
Pre Shot
Pre Shot Control
Shot 1
Shot Control
Shot 2
Shot Control
Shot 3
Shot Control
Shot 4
Shot Control
Shot 5
Shot Control
Shot 6
Shot Control
Service Alarm 1
Signal: AR - Service Alarm 1, too many switching operations
Service Alarm 2
Signal: AR - Service Alarm 2 - too many switching operations
Max Shots / h exceeded
Signal: The maximum allowed number of shots per hour has been
exceeded.
Res Statistics Cr
Signal: Reset all statistic AR counters: Total number of AR, successful and
unsuccessful no of AR.
Res Service Cr
Signal: Reset the Service Counters for Alarm and Blocking
Reset Lockout
Signal: The AR Lockout has been reset via the panel.
Res Max Shots / h
Signal: The Counter for the maximum allowed shots per hour has been
reset.
812
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...