Protective Elements
I - Overcurrent Protection [50, 51,51Q, 51V, 67]
Available stages:
I[1] ,I[2] ,I[3] ,I[4] ,I[5] ,I[6]
If you are using inrush blockings the tripping delay of the current protection
functions must be at least 30ms or more in order to prevent faulty trippings.
In order to ensure correct functioning of the directional detection after single-
phase short-circuits, the following reference voltage is used: For phase current
I1 it is the line-to-line voltage U23, for phase current I2 the line-to-line voltage
U31 and for phase current I3 the line-to-line voltage U12.
In case the fault happens to be near the measuring location and there is no
reference voltage for directional recognition available any more (neither
measured or from history (voltage memory)), then the module will - depending
on the parameter setting - either trip non-directional or it will be blocked.
All overcurrent protective elements are identically structured.
This module offers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
677
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...