Switchgear/Breaker – Manager
Parameter
Description
Setting range
Default
Menu path
Count6
Open Counts Allowed #6
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
Current7
Interrupted Current Level #7
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count7
Open Counts Allowed #7
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
Current8
Interrupted Current Level #8
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count8
Open Counts Allowed #8
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
Current9
Interrupted Current Level #9
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count9
Open Counts Allowed #9
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
Current10
Interrupted Current Level #10
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count10
Open Counts Allowed #10
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
517
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...