Specifications
Specifications of the Measured Value Acquisition
Phase and Ground Current Measuring
Frequency Range:
50 Hz / 60 Hz ± 10%
Accuracy:
Class 0.5
Amplitude Error if I < In:
±0.5% of the rated current
*3)
Amplitude Error if I > In:
±0.5% of the measured current
*3)
Amplitude Error if I > 2 In:
±1.0% of the measured current
*3)
Harmonics:
Up to 20% 3rd harmonic ±2%
Up to 20% 5th harmonic ±2%
Frequency Influence:
<±2% / Hz in the range of ±10% of the configured nominal frequency
Temperature Influence:
<±1% within the range of 0°C to +60°C (+32°F to +140°F)
*3
)
For earth current sensitive the precision does not depend on the nominal value but is referenced to 100 mA (with In =1 A) respectively. 500
mA (with In = 5 A)
Phase-to-ground and Residual Voltage Measurement
Frequency Range:
50 Hz / 60 Hz ± 10%
Accuracy for measured values:
Class 0.5
Amplitude error for V<Vn:
±0.5% of rated voltage or ±0.5 V
Amplitude error for V>Vn:
±0.5% of measured voltage or ±0.5 V
Accuracy for calculated values:
Class 1.0
Amplitude error for V<Vn:
±1.0% of rated voltage or ±1.0 V
Amplitude error for V>Vn:
±1.0% of calculated voltage or ±1.0 V
Harmonics:
Up to 20% 3rd harmonic ±1%
Up to 20% 5th harmonic ±1%
Frequency influence:
<±2% / Hz in the range of ±10% of the configured nominal frequency
Temperature influence:
<±1% within the range of 0°C up to +60°C
1254
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...