General Lists
Name
Description
CT Local.Phase seq.
wrong
Signal that the device has detected a phase sequence (L1-L2-L3 / L1-L3-L2) that is
different from the one that had been set at [Field settings / General Settings] »Phase
Sequence«.
Ctrl.Local
Switching Authority: Local
Ctrl.Remote
Switching Authority: Remote
Ctrl.NonInterl
Non-Interlocking is active
Ctrl.SG Indeterm
Minimum one Switchgear is moving (Position cannot be determined).
Ctrl.SG Disturb
Minimum one Switchgear is disturbed.
Ctrl.NonInterl-I
Non-Interlocking
SG[1].SI
SingleContactInd
Signal: The Position of the Switchgear is detected by one auxiliary contact (pole)
only. Thus indeterminate and disturbed Positions cannot be detected.
SG[1].Pos not ON
Signal: Pos not ON
SG[1].Pos ON
Signal: Circuit Breaker is in ON-Position
SG[1].Pos OFF
Signal: Circuit Breaker is in OFF-Position
SG[1].Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
SG[1].Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Breaker Position. The Position Indicators
contradict themselves. After expiring of a supervision timer this signal becomes true.
SG[1].Ready
Signal: Circuit breaker is ready for operation.
SG[1].t-Dwell
Signal: Dwell time
SG[1].Removed
Signal: The withdrawable circuit breaker is Removed
SG[1].Interl ON
Signal: One or more IL_On inputs are active.
SG[1].Interl OFF
Signal: One or more IL_Off inputs are active.
SG[1].CES succesf
Signal: Command Execution Supervision: Switching command executed successfully.
SG[1].CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful.
Switchgear in disturbed position.
SG[1].CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip
command is pending.
SG[1].CES SwitchDir
Signal: Command Execution Supervision respectively Switching Direction Control:
This signal becomes true, if a switch command is issued even though the switchgear
is already in the requested position. Example: A switchgear that is already OFF
should be switched OFF again (doubly). The same applies to CLOSE commands.
SG[1].CES ON d OFF
Signal: Command Execution Supervision: On Command during a pending OFF
Command.
SG[1].CES SG not ready Signal: Command Execution Supervision: Switchgear not ready
SG[1].CES Fiel Interl
Signal: Command Execution Supervision: Switching Command not executed because
of field interlocking.
SG[1].CES SyncTimeout Signal: Command Execution Supervision: Switching Command not executed. No
Synchronization signal while t-sync was running.
SG[1].CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful,
Switchgear removed.
SG[1].Prot ON
Signal: ON Command issued by the Prot module
SG[1].TripCmd
Signal: Trip Command
SG[1].Ack TripCmd
Signal: Acknowledge Trip Command
1158
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...