Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 10 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 10
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
11
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 11 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 11
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
12
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
364
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...