Communication Protocols
Point Mapping
Please take into account that the designations of inputs and outputs are set from the
Masters perspective. This way of choosing the designations is due to a definition in the
DNP standard. That means for example that Binary Inputs that can be set within the
Device Parameters of the DNP protocol are the “Binary Inputs” of the Master.
Call up menu [Device Para/DNP3/Point Map]. Once the general settings of the DNP protocol are done, the point
mapping is to be done as a next step.
•
Binary Inputs (States to be send to the master)
•
Double Bit Inputs (Breaker states to be send to the master)
•
Counters (Counters to be send to the master)
•
Analog Inputs (e.g. measured values to be send to the master). Please take into account that floating
values have to be transmitted as integers. That means they have to be scaled (multiplied) with a scaling
factor in order to bring them into the integer format.
Use Binary outputs in order to control e.g. LEDs or Relays within the protective device (via Logic).
344
MCDLV4
DOK-HB-MCDLV4-2E
DNP Master
Protective Relay
Point Mapping
Binary Inputs
Double Bit Inputs
Counters
Analog Inputs
B
in
a
ry
O
u
tp
ut
s
Pulse Signal
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...