Fault list – safety technology
Fault 68 Safe communication profile
Manual – Fault Descriptions MOVISAFE
®
CS..A
86
Subfault: 68.10
Description: Configuration and application of fieldbus slave not plausible
Fault class: Warning
Cause
Measure
Transferred configuration of fieldbus slave does
not match application of fieldbus slave.
Make sure that the parameter setting for the field-
bus slave is plausible with the fieldbus slave in
use.
Subfault: 68.164
Description: Different addresses for PROFIsafe communication (F_Dest_Add)
Fault class: Message
Cause
Measure
Different addresses for PROFIsafe communica-
tion (F_Dest_Add) in fieldbus master and fieldbus
slave.
Set the same address for PROFIsafe communi-
cation (F_Dest_Add) in the fieldbus master and
fieldbus slave.
Subfault: 68.165
Description: Invalid address for PROFIsafe communication (F_Dest_Add)
Fault class: Message
Cause
Measure
Invalid PROFIsafe communication address
(F_Dest_Add).
Set a valid address for PROFIsafe communica-
tion (F_Dest_Add).
Subfault: 68.166
Description: Invalid failsafe source address (F_Source_Add)
Fault class: Message
Cause
Measure
Failsafe source address (F_Source_Add) not
valid or different failsafe source addresses detect-
ed in fieldbus master and fieldbus slave.
– Set a valid failsafe source address
(F_Source_Add).
– Set the same failsafe source address in the
fieldbus master and fieldbus slave.
Subfault: 68.167
Description: Invalid watchdog time for PROFIsafe communication
Fault class: Message
Cause
Measure
Watchdog time for PROFIsafe communication
(F_WD_Time, F_WD_Time_2) is 0 ms.
Set a valid watchdog time for PROFIsafe commu-
nication (F_WD_Time, F_WD_Time_2) in the
fieldbus master.