2
Fault list – safety technology
Fault 61 Safe digital output
Manual – Fault Descriptions MOVISAFE
®
CS..A
43
Subfault: 61.11
Description: F-DO 00_P Short circuit
Fault class: Output fault
Cause
Measure
Short circuit in external wiring at P output of safe
digital output F-DO 00.
Check the external wiring at the P output of safe
digital output F-DO 00 for short circuit.
Subfault: 61.12
Description: F-DO 01_P Short circuit
Fault class: Output fault
Cause
Measure
Short circuit in external wiring at P output of safe
digital output F-DO 01.
Check the external wiring at the P output of safe
digital output F-DO 01 for short circuit.
Subfault: 61.21
Description: F-DO 00_M Short circuit
Fault class: Output fault
Cause
Measure
Short circuit in external wiring at M output of safe
digital output F-DO 00.
Check the external wiring at the M output of safe
digital output F-DO 00 for short circuit.
Subfault: 61.22
Description: F-DO 01_M Short circuit
Fault class: Output fault
Cause
Measure
Short circuit in external wiring at M output of safe
digital output F-DO 01.
Check the external wiring at the M output of safe
digital output F-DO 01 for short circuit.
Subfault: 61.31
Description: F-DO 00 Crossfault
Fault class: Output fault
Cause
Measure
Crossfault in external wiring of safe digital output
F‑DO 00. Excessive capacitive load or test dura-
tion too short.
– Check the external wiring of safe digital output
F‑DO 00 for crossfault.
– Check the parameter "Maximum test duration".
If the maximum response time allows for a longer
test duration, set this parameter to a greater
value.
– Make sure that the capacitance of the connect-
ed load does not exceed the value permitted for
the output.
27799182/EN – 10/2022