Fault list – safety technology
Fault 61 Safe digital output
Manual – Fault Descriptions MOVISAFE
®
CS..A
44
Subfault: 61.32
Description: F-DO 01 Crossfault
Fault class: Output fault
Cause
Measure
Crossfault in external wiring of safe digital output
F‑DO 01. Excessive capacitive load or test dura-
tion too short.
– Check the external wiring of safe digital output
F‑DO 01 for crossfault.
– Check the parameter "Maximum test duration".
If the maximum response time allows for a longer
test duration, set this parameter to a greater
value.
– Make sure that the capacitance of the connect-
ed load does not exceed the value permitted for
the output.
Subfault: 61.41
Description: F-DO 00_P Overcurrent
Fault class: Output fault
Cause
Measure
Permitted output current exceeded at P output of
safe digital output F-DO 00.
– Make sure that the current consumption of the
connected load does not exceed the permitted
output current. If necessary, change the load.
– Check the external wiring of safe digital output
F‑DO 00 for crossfault.
Subfault: 61.42
Description: F-DO 01_P Overcurrent
Fault class: Output fault
Cause
Measure
Permitted output current exceeded at P output of
safe digital output F-DO 01.
– Make sure that the current consumption of the
connected load does not exceed the permitted
output current. If necessary, change the load.
– Check the external wiring of safe digital output
F‑DO 01 for crossfault.
Subfault: 61.51
Description: F-DO 00_M Overcurrent
Fault class: Output fault
Cause
Measure
Permitted output current exceeded at M output of
safe digital output F-DO 00.
– Make sure that the current consumption of the
connected load does not exceed the permitted
output current. If necessary, change the load.
– Check the external wiring of safe digital output
F‑DO 00 for crossfault.