2
Fault list – safety technology
Fault 15 Encoder 3
Manual – Fault Descriptions MOVISAFE
®
CS..A
27
Subfault: 15.57
Description: Maximum speed exceeded
Response: FS – encoder fault
Cause
Measure
Permitted maximum speed exceeded.
– Check the maximum speed of the application
and adjust if necessary.
– Check the parameter setting of the safety card
and adjust if necessary.
Subfault: 15.58
Description: Detection limit exceeded
Response: FS – warning
Cause
Measure
Speed exceeded sensing limit.
– Check the maximum speed of the application
and adjust if necessary.
– Check the parameter setting of the safety card
and adjust if necessary.
Subfault: 15.59
Description: Encoder no longer referenced
Response: FS – warning
Cause
Measure
Diagnostics error detected during encoder evalu-
ation. Referencing is canceled.
– Remove the cause of the error.
– Reference the encoder again.
Subfault: 15.60
Description: Travel limit exceeded
Response: FS – encoder fault
Cause
Measure
Travel limit violated for an application with limited
travel distance.
– Check the startup parameters.
– Check the application.
– Perform referencing again.
Subfault: 15.61
Description: Wrong number of bits per telegram
Response: FS – warning
Cause
Measure
The number of bits received per telegram does
not match the number of parameterized bits.
– Check the startup parameters.
– Check the wiring.
– Check interference sources.
27799182/EN – 10/2022