2
Fault list – safety technology
Fault 67 Safe communication
Manual – Fault Descriptions MOVISAFE
®
CS..A
81
Subfault: 67.29
Description: F-PI data too short
Fault class: System error
Cause
Measure
F-profile variant needs more data than has been
received.
– Check the parameter setting of the safe control-
ler.
– Make sure that the slot of the HW configuration
accommodates the proper F‑module of the device
description file (GSDML file).
Subfault: 67.100
Description: Safety protocol message
Fault class: Message
Cause
Measure
Safety protocol signaled receipt of zero telegram
or connection not established correctly.
– Acknowledge the message.
– If the message occurs again, check the commu-
nication channel.
Subfault: 67.131
Description: CIP Safety™ configuration started
Response: No response
Cause
Measure
The user has activated the CIP Safety™ protocol. For information only.
Subfault: 67.140
Description: Restart by CIP Safety™
Response: FS – message
Cause
Measure
CIP Safety™ triggered a restart.
For information only.
Subfault: 67.141
Description: Error in safety stack control
Response: FS – message
Cause
Measure
Error in safety stack control (SSC) process.
For information only.
Subfault: 67.142
Description: Error in safety validator connection establishment engine
Response: FS – message
Cause
Measure
Error in SCE in safety open sequence in content
of receive data or in transmission of response
data.
For information only.
27799182/EN – 10/2022