Fault list – safety technology
Fault 69 Micro controller or diagnostics error
Manual – Fault Descriptions MOVISAFE
®
CS..A
88
Subfault: 68.176
Description: Safety parameter "F_Block_ID" not supported
Fault class: Message
Cause
Measure
Safety parameter "F_Block_ID" not supported.
Check the safety parameters in the configuration
tool of the fieldbus master.
Subfault: 68.177
Description: Error due to transfer of inconsistent data
Fault class: Message
Cause
Measure
Data of sent safety parameters not consistent.
Check the safety parameters in the configuration
tool of the fieldbus master.
Subfault: 68.178
Description: Watchdog time exceeded while transferring data
Fault class: Message
Cause
Measure
Watchdog time exceeded (F_WD_Time,
F_WD_Time_2) while transferring data.
Check the safety parameters in the configuration
tool of the fieldbus master.
2.18
Fault 69 Micro controller or diagnostics error
Subfault: 69.1
Description: Processor error
Fault class: System error
Cause
Measure
Error in processor.
– Switch the device off and on again.
– If the fault occurs repeatedly, replace the safety
card and send it together with the fault number to
SEW‑EURODRIVE. For further support, contact
SEW‑EURODRIVE Service.
Subfault: 69.2
Description: Flash memory error
Fault class: Critical fault
Cause
Measure
Error in flash memory.
– Switch the device off and on again.
– If the fault occurs repeatedly, replace the safety
card and send it together with the fault number to
SEW‑EURODRIVE. For further support, contact
SEW‑EURODRIVE Service.
27799182/EN – 10/2022