2
Fault list – safety technology
Fault 66 Safety-related fault
Manual – Fault Descriptions MOVISAFE
®
CS..A
68
Subfault: 66.35
Description: Data storage plausibility check failed
Fault class: Critical fault
Cause
Measure
Values of data storage do not match expected
values.
– Switch the device off and on again.
– If the fault occurs repeatedly, replace the safety
card and send it together with the fault number to
SEW‑EURODRIVE. For further support, contact
SEW‑EURODRIVE Service.
Subfault: 66.36
Description: Faulty hardware ID
Fault class: Critical fault
Cause
Measure
Hardware defective.
Replace the safety card and send it together with
the fault number to SEW‑EURODRIVE. For fur-
ther support, contact SEW‑EURODRIVE Service.
Subfault: 66.38
Description: Faulty application parameter setting
Fault class: System error
Cause
Measure
Faulty application parameters read from data
memory.
Transfer the data set to the safety card again us-
ing the "Assist CS.." tool.
Subfault: 66.39
Description: Faulty data from safety key
Fault class: System error
Cause
Measure
Faulty data read from safety key.
Transfer the data set to the safety card again us-
ing the "Assist CS.." tool.
Subfault: 66.40
Description: Error saving application parameters
Fault class: System error
Cause
Measure
Error saving application parameters.
Transfer the data set to the safety card again us-
ing the "Assist CS.." tool.
Subfault: 66.41
Description: Error saving key
Fault class: System error
Cause
Measure
Error saving key to safety key.
Transfer the data set to the safety card again us-
ing the "Assist CS.." tool.
27799182/EN – 10/2022