6 - 61
6 Troubleshooting
NJ-series NJ Robotics CPU Unit User’s Manual (W539)
6-2
Er
ro
r Descript
ion
6
6-
2-2 Err
or D
escriptions
Event name
Current Position Outside Workspace
Event code
67010000 hex
Meaning
The current position was outside the workspace when an instruction was executed.
Source
Motion Control Function Module
Source details
Axes group
Detection
timing
At instruction
execution
Error
attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
Operation is not possible for relevant axes group.
Relevant axes group stops immediately if it is in
motion.
System-
defined
variables
Variable
Data type
Name
_MC_GRP[*].MFaultLvl.Active
BOOL
Axes Group Minor Fault Occur-
rence
Cause and
correction
Assumed cause
Correction
Prevention
The current position was outside
the workspace when one of the
following robot instructions was
executed.
• MC_MoveTimeAbsolute
(Time-specified Absolute Posi-
tioning) instruction
• MC_SyncLinearConveyor (Start
Conveyor Synchronization)
instruction
• MC_SyncOut (End Synchroni-
zation) instruction
• MC_RobotJog (Axes Group
Jog) instruction
Move the robot inside the work-
space.
Review the program and make
sure that the robot moves within
the range of the workspace.
Attached
information
None
Precautions/
Remarks
None
Summary of Contents for NJ501-4300
Page 13: ...11 CONTENTS NJ series NJ Robotics CPU Unit User s Manual W539 ...
Page 40: ...Revision History 38 NJ series NJ Robotics CPU Unit User s Manual W539 ...
Page 90: ...2 Features of NJ Robotics CPU Unit 2 40 NJ series NJ Robotics CPU Unit User s Manual W539 ...
Page 204: ...5 Vision Robot Integrated Simulation 5 6 NJ series NJ Robotics CPU Unit User s Manual W539 ...
Page 308: ...6 Troubleshooting 6 104 NJ series NJ Robotics CPU Unit User s Manual W539 ...
Page 333: ...I 1 I NJ series NJ Robotics CPU Unit User s Manual W539 Index ...
Page 335: ......