A - 25
Appendices
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User’s Manual
A
-2 P
arameter Lis
t
A
506
Stop Selection
with Servo OFF
Set the stop operation to be performed when
the servo is OFF.
0
–
0 to 9
–
0
During deceleration: Dynamic brake
After stopping: Dynamic brake
Error counter: Clear
1
During deceleration: Free-run
After stopping: Dynamic brake
Error counter: Clear
2
During deceleration: Dynamic brake
After stopping: Servo-free
Error counter: Clear
3
During deceleration: Free-run
After stopping: Servo-free
Error counter: Clear
4
During deceleration: Dynamic brake
After stopping: Dynamic brake
Error counter: Hold
5
During deceleration: Free-run
After stopping: Dynamic brake
Error counter: Hold
6
During deceleration: Dynamic brake
After stopping: Servo-free
Error counter: Hold
7
During deceleration: Free-run
After stopping: Servo-free
Error counter: Hold
8
During deceleration: Emergency stop
After stopping: Dynamic brake
Error counter: Clear
9
During deceleration: Emergency stop
After stopping: Servo-free
Error counter: Clear
507
Stop Selection
with Main
Power Supply
OFF
Set the stop operation to be performed when
the main power supply is turned OFF.
The set values for this parameter are the same
as those of Stop Selection with Servo OFF
(Pn506).
0
–
0 to 9
–
508
Undervoltage
Alarm
Selection
Select whether to allow an LV trip or turn OFF
the servo when a main power supply alarm
occurs.
1
–
0 to 1
–
509
Momentary
Hold Time
Set the Main Power Supply Alarm detection
time.
70
1 ms
70 to
2,000
Required
Pn
No.
Name
Setting
Description
Default
setting
Unit
Setting
range
Cycle the
power
supply