5 Basic Control Mode
5 - 8
OMNUC G5-series (Pulse-train Input Type) AC Servomotors and Servo Drives User’s Manual
The following tables show the internally set speeds that are set with VSEL1, VSEL2 and VSEL3
(internally set speed selection 1, 2 and 3).
Pn300 =1
Pn300 = 3
• Internally set speed control with 4 speed changes when Pn300 is set to 1
*1
The acceleration time, deceleration time, and S-curve acceleration/deceleration time can be set in parameters
Pn312, Pn313, and Pn314, respectively.
Internally Set Speed Selection
No.
VSEL1
VSEL2
VSEL3
Set speed
0
OFF
OFF
Disabled
Pn304
1
ON
OFF
Disabled
Pn305
2
OFF
ON
Disabled
Pn306
3
ON
ON
Disabled
Pn307
No.
VSEL1
VSEL2
VSEL3
Set speed
0
OFF
OFF
OFF
Pn304
1
ON
OFF
OFF
Pn305
2
OFF
ON
OFF
Pn306
3
ON
ON
OFF
Pn307
4
OFF
OFF
ON
Pn308
5
ON
OFF
ON
Pn309
6
OFF
ON
ON
Pn310
7
ON
ON
ON
Pn311
Operation Example
Operation Command (RUN)
Zero Speed Specified (VZERO)
Internally Set Speed Selection 1 (VSEL1)
Internally Set Speed Selection 2 (VSEL2)
Servo ON
Drive
Stop
Speed
Open
Open
Speed 1
Speed 2
Speed 4
Speed 3
Time t
Closed
Closed
Closed
Closed
Open
Open
(*1)