• If you are hot-removing a disk shelf from a stack (but keeping the stack), you recable and verify one path at
a time (path A then path B) to bypass the disk shelf you are removing so that you always maintain single-
path connectivity from the controllers to the stack.
If you do not maintain single-path connectivity from the controllers to the stack when
recabling the stack to bypass the disk shelf you are removing, you could fail the system with
a multidisk panic.
Steps
1. Verify that your system configuration is
Multi-Path HA
,
Multi-Path
,
Quad-path HA
, or
Quad-path
:
sysconfig
You run this command from the nodeshell of either controller. It might take up to a minute for the system to
complete discovery.
The configuration is listed in the
System Storage Configuration
field.
For a FAS2600 series single-controller system that has the external storage cabled with
multipath connectivity, the output is displayed as
mixed-path
because the internal storage
uses single-path connectivity.
2. Verify that the disk drives in the disk shelves you are removing have no aggregates (are spares) and
ownership is removed:
a. Enter the following command from the clustershell of either controller:
storage disk show -shelf
shelf_number
b. Check the output to verify that there are no aggregates on the disk drives in the disk shelves you are
removing.
Disk drives with no aggregates have a dash in the
Container Name
column.
c. Check the output to verify that ownership is removed from the disk drives on the disk shelves you are
removing.
Disk drives with no ownership have a dash in the
Owner
column.
If you have failed disk drives in the shelf you are removing, they have broken in the
Container Type
column. (Failed disk drive do not have ownership.)
The following output shows disk drives on the disk shelf being removed (disk shelf 3) are in a correct state
for removing the disk shelf. The aggregates are removed on all of the disk drives; therefore, a dash
appears in the
Container Name
column for each disk drive. Ownership is also removed on all of the disk
drives; therefore, a dash appears in the
Owner
column for each disk drive.
1648
Summary of Contents for AFF A700
Page 4: ...AFF and FAS System Documentation 1...
Page 208: ...3 Close the controller module cover and tighten the thumbscrew 205...
Page 248: ...2 Close the controller module cover and tighten the thumbscrew 245...
Page 308: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 305...
Page 381: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 378...
Page 437: ...1 Locate the DIMMs on your controller module 434...
Page 605: ...602...
Page 1117: ...3 Close the controller module cover and tighten the thumbscrew 1114...
Page 1157: ...2 Close the controller module cover and tighten the thumbscrew 1154...
Page 1228: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 1225...
Page 1300: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 1297...
Page 1462: ...Installing SuperRail to round hole four post rack 1459...
Page 1602: ...1599...
Page 1630: ...1627...
Page 1634: ...Orange ring on horizontal bracket Cable chain 1631...
Page 1645: ...Guide rail 1642...
Page 1669: ...Attention LED light on 1666...