120
1 SERVO PARAMETER DETAILS
1.7 Extension setting 3 servo parameters group ([Pr. PF_ _ ])
[Pr. PF18_STO diagnosis error detection time (**STOD)]
Set the time from when the error of the STO input or STO circuit is detected until the occurrence of [AL. 068.1 STO signal
mismatch error].
When "0" is set, [AL. 068.1] is not detected.
The safety level depends on the setting value of this servo parameter and whether STO input diagnosis is performed by TOFB
output as shown in the following table.
When the STO function is not used with the short-circuit connector connected to the CN8 connector, the safety level does not
change even after setting this servo parameter.
This servo parameter cannot be used with the MR-J5-_G_-RJ, MR-J5W_-G_, or MR-J5D_-_G_.
The alarm occurs when an STO input error is detected.
Refer to the following table for details.
Page 226 [Pr. PSA01.0_Safety sub-function activation setting]
Page 242 [Pr. PSD18_Permissible time for mismatches DI1 (**SDIDT1)]
[Pr. PF19_Friction failure prediction - Compensation coefficient 1
(TSL)]
Set compensation coefficient 1 to compensate the dynamic friction being used for the friction failure prediction.
When the friction failure prediction warning selection is set to the automatic threshold setting, the value will be calculated
automatically from the estimated dynamic friction.
When performing threshold manual setting on an equipment for which the threshold setting has been made once, set the
value that has been calculated by the threshold automatic setting.
Setting this servo parameter decreases the possibility of erroneous detection of friction failure prediction, even with the
manual threshold setting.
Initial value
Setting range
Setting method
Ver.
10 [s]
0 to 60
Common
A0
Setting value
STO input diagnosis by TOFB
output
Safety level
0
Execute
EN ISO 13849-1:2015 Category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2,
and EN 61800-5-2 SIL 2
Do not execute
1 to 60
Execute
EN ISO 13849-1:2015 Category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL 3,
and EN 61800-5-2 SIL 3
Do not execute
EN ISO 13849-1:2015 Category 3 PL d, IEC 61508 SIL 2, and EN 62061 SIL
CL 2
Model
Firmware version
Setting of [Pr.
PSA01.0]
Parameter to be
used
Time required
for alarm to
occur
Alarm to occur
MR-J5-_G_
Servo amplifiers with version A0
or later
[Pr. PF18]
0 to 60 s
[AL. 068.1]
MR-J5-_G_-RJ
MR-J5W_-G_
MR-J5D_-_G_
Servo amplifiers with versions
earlier than B2
Fixed as 10 s
[AL. 557]
Servo amplifiers with version B2
or later
0: Disabled
Fixed as 10 s
[AL. 557]
1: Enabled
[Pr. PSD18]
0 to 60000 ms
[AL. 557]
Initial value
Setting range
Setting method
Ver.
0 [0.0001 %/°C]
-32768 to 32767
Each axis
A0