1 SERVO PARAMETER DETAILS
1.4 Extension setting servo parameters group ([Pr. PC_ _ ])
[Pr. PC20.6_Input open-phase status output selection]
Select the conditions to turn on bit 10 (S_PNL) of [Status DO 5 (Obj. 2D15h)].
When turning on the bit in an input open-phase state due to incorrect wiring or disconnection, set this servo parameter to "0"
or "2".
When turning on the bit in an input open-phase state due to turning off of the main circuit power supply, set this servo
parameter to "1" or "3".
0: Turn on during servo-on and when one phase is open
1: Turn on during servo-on and when one, two, or all phases are open
2: Turn on when one phase is open
3: Turn on when one, two, or all phases are open
While [Pr. PC20.4 Input open-phase detection selection] is set to "3" (disabled), bit 10 (S_PNLT) of [Status DO 5] does not
turn on when one phase is open. To turn on bit 10 (S_PNLT) of [Status DO 5] when one phase is open, set [Pr. PC20.4] to "1"
(warning enabled) or "2" (alarm enabled).
For the MR-J5D_-_G_, bit 10 (S_PNLT) of [Status DO 5] is always off.
While the detection function is enabled in [Pr. PC20.4], bit 10 (S_PNLT) of [Status DO 5] is always on if being used with 1-
phase AC input. When using the bit with 1-phase AC input, set [Pr. PC20.4] to "3" (disabled).
[Pr. PC21_Alarm history clear (*BPS)]
[Pr. PC21.0_Alarm clear history selection]
0: Disabled
1: Enabled
When "1" (enabled) is selected, the alarm history will be cleared at either the next power cycle, at software reset, or at
controller reset. After the alarm history is cleared, "0" (disabled) will be set to this servo parameter automatically.