1 SERVO PARAMETER DETAILS
1.6 Extension setting 2 servo parameters group ([Pr. PE_ _ ])
1.6
Extension setting 2 servo parameters group ([Pr.
PE_ _ ])
[Pr. PE01_Fully closed loop control function selection 1 (**FCT1)]
[Pr. PE01.0_Fully closed loop function selection]
Select the fully closed loop function.
This servo parameter is enabled when [Pr. PA01.4 Fully closed loop operation mode selection] is set to "1" (enabled (fully
closed loop control mode)).
If this servo parameter is set to "1" while [Pr. PA03.0 Absolute position detection system selection] has been set to "1"
(enabled (absolute position detection system)), [AL. 037 Parameter error].
If semi-closed loop control/fully closed loop control switching is performed during operation in the homing mode or the profile
position mode while this servo parameter is set to "1", [AL. 0F4.A Fully closed loop control - Switching warning] occurs. In this
case, the control method does not switch to the selected control method while the operation is in progress.
When the positioning mode (point table method) is selected, setting this servo parameter to "1" triggers [AL. 037].
0: Always enabled
1: Switching by "fully closed loop selection" from the controller (C_CLD) and by the input device "fully closed loop selection"
(CLD)
*1 This is always off if CLD (fully closed loop selection) is not assigned to an input device pin.
Initial value
Setting range
Setting method
Ver.
00000000h
Refer to the relevant detail No.
Each axis
Refer to the relevant detail No.
Initial value
Setting range
Ver.
0h
Refer to the text
A5
Fully closed loop selection
Control method
Command from controller (C_CLD)
CLD (fully closed loop selection)
OFF
OFF
Semi closed loop control
ON
OFF
Fully closed loop control
OFF
ON
ON
ON