1 SERVO PARAMETER DETAILS
1.4 Extension setting servo parameters group ([Pr. PC_ _ ])
85
1
[Pr. PC46_Drive unit function selection 2 (*DUOP2)]
[Pr. PC46.1_Converter stop mode selection]
Select the converter stop mode.
0: Converter main circuit MC off in occurrence of the converter stop alarm
1: Converter main circuit MC off in occurrence of an alarm
This servo parameter can be used only with the MR-J5D_-_G_. The setting value of this servo parameter is disabled for servo
amplifiers other than the MR-J5D_-_G_.
When this servo parameter is set to "1", all alarms are applicable to converter main circuit stop. Alternatively, the motor stop
method of all the alarms changes to DB (Dynamic brake stop). For the alarms applicable to converter main circuit stop and
motor stop methods, refer to "List of alarm No./warning No." in the following manual.
MR-J5 User's Manual (Troubleshooting)
[Pr. PC46.2_Protection coordination multiple connection selection]
When connecting multiple MR-J5D_-_G_ to one converter unit using a protection coordination cable, set this servo parameter
to "1".
0: Connect one MR-J5D_-_G_ to one converter unit.
1: Connect multiple MR-J5D_-_G_ to one converter unit.
This servo parameter can be used only with the MR-J5D_-_G_. The setting value of this servo parameter is disabled for servo
amplifiers other than the MR-J5D_-_G_.
When this servo parameter is set to "1", the motor stop method of the alarm changes to DB (Dynamic brake stop) if all axes
are specified for the stop system. For the motor stop method, refer to "List of alarm No./warning No." in the following manual.
MR-J5 User's Manual (Troubleshooting)
[Pr. PC46.3_Protection coordination end terminal setting]
When connecting multiple MR-J5D_-_G_ to one converter unit using a protection coordination cable, set this servo parameter
to "1" on the end terminal drive unit.
0: Terminal settings disabled
1: Terminal settings enabled (end terminal)
This servo parameter can be used only with the MR-J5D_-_G_. The setting value of this servo parameter is disabled for servo
amplifiers other than the MR-J5D_-_G_.
This servo parameter is enabled only when [Pr. PC46.2 Protection coordination multiple connections selection] is set to "1"
(connect multiple MR-J5D_-_G_ to the converter unit). The setting value of this servo parameter is disabled when [Pr.
PC46.2] is set to "0" (connect one MR-J5D_-_G_ to one converter unit).
If the setting value of this servo parameter does not match the connection status of the protection coordination cable, [AL. 11B
Protection coordination connection error] occurs.
Initial value
Setting range
Setting method
Ver.
00000000h
Refer to the relevant detail No.
Common
Refer to the relevant detail No.
Initial value
Setting range
Ver.
0h
Refer to the text
C0
Initial value
Setting range
Ver.
0h
Refer to the text
C0
Initial value
Setting range
Ver.
0h
Refer to the text
C0