7 FUNCTIONAL SAFETY PARAMETER DETAILS
7.4 Safety I/O device parameters group ([Pr. PSD_ _ ])
241
7
[Pr. PSD08.3_Output axis selection DO1]
0: All axes
1: A-axis
2: B-axis
3: C-axis
If the setting value is 1, the device name is _ _ _-A. (example: "STOS-A")
If the setting value is 2, the device name is _ _ _-B. (example: "STOS-B")
If the setting value is 3, the device name is _ _ _-C. (example: "STOS-C")
[Pr. PSD12_Input device - Noise elimination filter time DI1
(**SDIF1)]
Select the filter time to use for reducing noise from the input signal of the CN8-4/CN8-5 pin.
Refer to the following table for details.
[Pr. PSD12.0-1_Noise elimination filter time DI1]
Select the filter time for the input signal of the CN8-4/CN8-5 pin.
Refer to the following table for setting values.
Initial value
Setting range
Ver.
0h
Refer to the text
B2
Initial value
Setting range
Setting method
Ver.
00000001h
Refer to the relevant detail No.
Common
Refer to the relevant detail No.
Configuration
Noise elimination filter time
Using a switch
Set 1.00 ms or more.
Using a machine utilizing the diagnosis function
Test pulses are in superposition in the output signal
of the device.
Set a time that is at least 1.00 ms longer than the
off time for test pulses output by the machine.
Test pulses are not in superposition in the output
signal of the device.
Set 1.00 ms or more.
Initial value
Setting range
Ver.
01h
Refer to the text
B2
Setting value
Filtering time [ms]
00
1.000
01
2.000
02
4.000
03
8.000
04
16.000
05
32.000