1 SERVO PARAMETER DETAILS
1.4 Extension setting servo parameters group ([Pr. PC_ _ ])
77
1
[Pr. PC20_Function selection C-7 (*COP7)]
[Pr. PC20.2_Undervoltage alarm selection]
Select the alarm or warning that occurs when the bus voltage drops to the undervoltage alarm trigger level.
0: [AL. 010 Undervoltage] occurs regardless of servo motor speed
1: [AL. 0E9 Main circuit off warning] occurs when the servo motor speed is 50 r/min (50 mm/s) or less, and [AL. 010] occurs
when over 50 r/min (50 mm/s).
[Pr. PC20.4_Input open-phase detection selection]
Enable or disable the detection of input open-phase detection function.
Setting this servo parameter to "1" or "2" on the MR-J5D_-_G_ triggers [AL. 037 Parameter error].
0: Automatic
1: Warning enabled
2: Alarm enabled
3: Disabled
When "0" (automatic) is set, the input open-phase detection function is enabled or disabled depending on the capacity or
power supply input of the servo amplifier. Details are as follows.
Initial value
Setting range
Setting method
Ver.
00000000h
Refer to the relevant detail No.
Common
Refer to the relevant detail No.
Initial value
Setting range
Ver.
0h
Refer to the text
A0
Initial value
Setting range
Ver.
0h
Refer to the text
A0
Servo amplifier
Servo amplifier main circuit
input voltage
Servo amplifier capacity
Input open-phase detection
function
MR-J5-_G(-RJ_)
3-phase AC
2 kW or less
Disabled
1-phase AC
Main circuit DC
2 kW or less
Disabled
3-phase AC
3.5 kW or more
Warning occurrence
Main circuit DC
3.5 kW or more
Disabled
MR-J5W_-_G_
3-phase AC
0.75 kW or less
Disabled
1-phase AC
Main circuit DC
0.75 kW or less
Disabled
3-phase AC
1 kW or more
Warning occurrence
Main circuit DC
1 kW or more
Disabled
MR-J5-_G4(-RJ_)
3-phase AC
3.5 kW or less
Warning occurrence
MR-J5D_-_G_
Disabled