C-4
ALPS Advanced Line Protection System
GE Power Management
C.2 DEVICE PROFILE
APPENDIX C
C
C.2.2 IMPLEMENTATION TABLE
The implementation table gives a list of all objects recognized and returned by the ALPS device. Additional information
detailing a list of default variations returned for each object and lists of defined point numbers for each object is provided on
the following pages.
Table C–1: IMPLEMENTATION TABLE
OBJECT
REQUEST
RESPONSE
OBJ
VAR
DESCRIPTION
FUNC CODES
(DEC)
QUAL CODES
(HEX)
FUNC CODES
(DEC)
QUAL CODES
(HEX)
1
0
Binary Input – All Variations
1
06
1
1
Binary Input
1
00, 01, 06
129
00, 01
1
2
Binary Input With Status
1
00, 01, 06
129
00, 01
2
0
Binary Input Change – All Variations
1
06, 07, 08
2
1
Binary Input Change Without Time
1
06, 07, 08
129
17, 28
2
2
Binary Input Change With Time
1
06, 07, 08
129
17, 28
10
0
Binary Output – All Variations
1
06
10
2
Binary Output Status
1
00, 01, 06
129
00, 01
12
1
Control Relay Output Block
5, 6
17, 28
129
17, 28
20
0
Binary Counter – All Variations
1, 7, 8, 9, 10
06
129
00, 01
20
5
32-Bit Binary Counter without Flag
1, 7, 8, 9, 10
06
129
00, 01
20
6
16-Bit Binary Counter without Flag
1, 7, 8, 9, 10
06
129
00, 01
21
0
Frozen Counter – All Variations
1
06
129
00, 01
21
9
32-Bit Frozen Counter without Flag
1
06
129
00, 01
21
10
16-Bit Frozen Counter without Flag
1
06
129
00, 01
30
0
Analog Input – All Variations
1
06
30
1
32-Bit Analog Input with Flag
1
00, 01, 06
129
00, 01
30
2
16-Bit Analog Input with Flag
1
00, 01, 06
129
00, 01
30
3
32-Bit Analog Input without Flag
1
00, 01, 06
129
00, 01
30
4
16-Bit Analog Input without Flag
1
00, 01, 06
129
00, 01
32
0
Analog Change Event – All Variations
1
06, 07, 08
32
1
32-Bit Analog Change Event without Time
1
06, 07, 08
129
17, 28
32
2
16-Bit Analog Change Event without Time
1
06, 07, 08
129
17, 28
32
3
32-Bit Analog Change Event with Time
1
06, 07, 08
129
17, 28
32
4
16-Bit Analog Change Event with Time
1
06, 07, 08
129
17, 28
40
0
Analog Output Status – All Variations
1
06
40
1
32-Bit Analog Output Status
1
00, 01, 06
129
00, 01
40
2
16-Bit Analog Output Status
1
00, 01, 06
129
00, 01
41
1
32-Bit Analog Output Block
5, 6
17, 28
129
17, 28
41
2
16-Bit Analog Output Block
5, 6
17, 28
129
17, 28
50
1
Time And Date
1, 2
07
1
129
07
60
1
Class 0 Data
2
1
06
60
2
Class 1 Data
3
1
06, 07,. 08
129
60
3
Class 2 Data
3
1
06, 07, 08
129
60
4
Class 3 Data
3
1
06, 07, 08
129
80
1
Internal Indications
2
00
4
129
No Object (Cold Start Command)
13
No Object (Warm Start Command)
5
14
No Object (Delay Measurement Command)
6
23
1
,
2
,
3
,
4
,
5
,
6
See IMPLEMENTATION TABLE NOTES section on the following page