2-62
ALPS Advanced Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
1817
HOLDSENSE
Contact Input Status
CC, CO
CC
1818
SYNCCHECK
Synch Check Supervision
NO, YES
NO
1819
CLOSEANG
Closing Angle
0 to 75 deg. step 1
30 deg.
1820
SLIPFREQ
Slip Frequency
0.1 to 5 Hz step 0.1
1 Hz
1821
BUSLINE
Bus or Line Voltage
BUS, LINE
LINE
1822
SYNCPHASE
Voltage used by SYNCCHECK
VA, VB, VC, VAB, VBC, VCA
VA
1823
SYNCHOLD
SYNCCHECK Hold Time
1 to 100 sec. step 1
1 sec.
1824
^
SP1DELAY2
Supervise 2nd 3P Reclose after
1P Trip
NO, YES
NO
1825
^
SP1DELAY3
Supervise 3rd 3P Reclose after 1P
Trip
NO, YES
NO
1826
^
SP1DELAY4
Supervise 4th 3P Reclose after 1P
Trip
NO, YES
NO
1827
SP3DELAY1
Supervise 1st 3P Reclose after 3P
Trip
NO, YES
NO
1828
SP3DELAY2
Supervise 2nd 3P Reclose after
3P Trip
NO, YES
NO
1829
SP3DELAY3
Supervise 3rd 3P Reclose after 3P
Trip
NO, YES
NO
1830
SP3DELAY4
Supervise 4th 3P Reclose after 3P
Trip
NO, YES
NO
1831
SYNCMANCLS
Supervise Manual Close
NO, YES
NO
1832
VBUSLIVE
Live Bus Voltage
0.1 to 130 volts step 0.1
50 V
1833
VBUSDEAD
Dead Bus Voltage
0.1 to 130 volts step 0.1
50 V
1834
VLINELIVE
Live Line Voltage
0.1 to 130 volts step 0.1
50 V
1835
VLINEDEAD
Dead Line Voltage
0.1 to 130 volts step 0.1
50 V
1836
LBUSDLINE
Live Bus Dead Line
NO, YES
NO
1837
DBUSLLINE
Dead Bus Live Line
NO, YES
NO
1838
DBUSDLINE
Dead Bus Dead Line
NO, YES
NO
1839
DELTAV
Voltage Difference
0.1 to 30 volts step 0.1
10 V
1840
DELTAVBLK
Block Synch Check by DELTAV
NO, YES
NO
NONCRIT_AL
1901
NCAIN1
Non-Critical Alarm Input #1
These 8 inputs are ORed together
and then outputted to the contact
assigned to the Non-Critical Alarm
0 to 256 step 1
48
1902
NCAIN2
Non-Critical Alarm Input #2
0 to 256 step 1
49
1903
NCAIN3
Non-Critical Alarm Input #3
0 to 256 step 1
50
1904
NCAIN4
Non-Critical Alarm Input #4
0 to 256 step 1
51
1905
NCAIN5
Non-Critical Alarm Input #5
0 to 256 step 1
1906
NCAIN6
Non-Critical Alarm Input #6
0 to 256 step 1
1907
NCAIN7
Non-Critical Alarm Input #7
0 to 256 step 1
1908
NCAIN8
Non-Critical Alarm Input #8
0 to 256 step 1
OUTPUTS
2001
T1
T1 Contract
0 to 256 step 1
33
2002
T2
T2 Contact
0 to 256 step 1
33
2003
T3
T3 Contact
0 to 256 step 1
33
2004
T4
T4 Contact
0 to 256 step 1
33
2005
^
T5
T5 Contact
0 to 256 step 1
34
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 6 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
DEFAULT
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.